Week 14–15
RMS, AC power, transformers, three-phase
Power in AC circuits. RMS values let you reuse DC power formulas, and phasors from week 7 split a load's power into real power P (watts, used only by resistors) and reactive power Q (VAR, traded back and forth by capacitors and inductors). Together they give complex power S, apparent power |S| and the power factor, which you correct with a parallel capacitor. The weeks finish with ideal transformers (voltage, current and impedance ratios, VA ratings), household wiring, and three-phase wye and delta systems, the last for information only.
Objectives
- Compute the RMS value of sinusoidal, triangular, square, AC-plus-DC and arbitrary piecewise waveforms, and use it to find the average power and energy delivered to a resistor.
- Explain why an average-responding meter reads correctly only for sine waves, using the rectified average of sine, triangle and square waves.
- Calculate real power P, reactive power Q, complex power S, apparent power |S| and power factor for a load given its impedance, its complex power, or voltmeter, ammeter and wattmeter readings, and draw the power phasor diagram.
- Decide whether a load's power factor is leading or lagging from the sign of Q or the load type (capacitive or inductive).
- Size a capacitor (or inductor) in parallel with a load to correct its power factor to 1 or to a target such as 0.9 lagging at 60 Hz, without changing the real power.
- Apply the ideal transformer relations N1/N2 = V1/V2 = I2/I1 to find turns, voltages and currents, including rms conversion of a peak input.
- Reflect a secondary load into the primary with Zeq = (N1/N2)²Z2 and solve a transformer circuit with series source resistance for currents, voltages, power and the power factor seen by the source.
- Check whether a transformer operates within its V and VA ratings, and find the maximum current and usable power it can deliver at a given power factor.
- Relate line-to-line and line-to-neutral voltages, line and phase currents, and total power in balanced wye and delta three-phase systems.
Reading
| 2.21–22 | RMS voltage and current for resistors in AC circuits, and mains power. Focus on why Vrms = Vp/√2 and on 120 V, 60 Hz household numbers. |
| 2.28 | Power in AC circuits: apparent, real and reactive power and power factor. This is the core reading; PA1 also asks you to start about 1.5 pages earlier in 2.27.3 at "Series Impedance (RL circuit)". |
| 3.8 | Transformers: basic operation, construction, autotransformers and variable transformers, isolation transformers and applications. Note the instructor's warning that the text draws secondary windings and currents backwards. |
| app. A | Power distribution and home wiring: why distribution is AC at high voltage, three-phase generation, household wiring, and electricity in other countries. Read for context; three-phase is FYI in this course. |
Lectures
| 1 | AC power introOpen original recording | 51:46 |
| 2 | AC power examplesOpen original recording | 1:02:14 |
| 3 | TransformersOpen original recording | 51:48 |
| 2:45:48 |
Notes
From the notes pack:
- DC power versus AC power into a resistor, and the effective (RMS) voltage: root of the mean of the square
- RMS of a sinusoid derived: Vrms = Vp/√2
- Household power: 60 Hz, ω = 377 rad/s, 120 V rms (170 V peak), outlet line, neutral and ground
- RMS of triangular and sawtooth waves (Vp/√3), square waves and DC (Vp), and AC plus DC (√(Vrms,AC² + VDC²))
- Rectified average values and why most AC meters read 1.11 times the rectified average, correct only for sine waves
- Worked RMS and DC average of a piecewise square wave, and the power and energy it delivers to a 50 Ω resistor
- Capacitors and inductors take zero average power; reactive power QC = −IC²/(ωC) is negative and QL = IL²ωL is positive
- Only the in-phase part of the current carries power (dot product), lagging versus leading
- Definitions with RMS values: P = VI cos θ, Q = VI sin θ, S = VI* = P + jQ, |S| = √(P² + Q²), pf = cos θ
- Power factor: leading for capacitive loads, lagging for inductive loads (the usual case), why pf below 1 costs utilities and industrial users, and correction with parallel capacitors
- Transformer basics: rated V and VA, ideal transformer P1 = P2, voltage and current ratios, turns-ratio conventions
- Impedance transformation Zeq = (N1/N2)²Z2 and impedance matching
- Other transformers: multi-tap, isolation, autotransformer, Variac, LVDT position sensor
- Home power: +120 V, ground and −120 V (180° apart, giving 240 V), not three-phase
- Three-phase power (FYI only): constant power with balanced loads, wye and delta connections, VLL = √3 VLN, 208 V and 480 V systems, three-phase P, Q and S
- AC power examples 1 and 2: parallel and series RL loads on 110 V, find P, Q, S, |S|, pf and the parallel capacitor for pf = 1
- AC power examples 3 to 5: loads measured with voltmeter, ammeter and wattmeter; find R, X, powers, leading or lagging, and the correcting component
- AC power examples 6 and 7: step-down transformer turns, currents and ratings; ideal transformer circuit solved with reflected impedance
Homework
PA1: AC power and power factor
- Read the AC power notes and examples and text sections 2.27.3 (from "Series Impedance (RL circuit)") and 2.28
- Compute the power factor of a series 20 mH and 6 Ω inductive load at ω = 377 rad/s
- A load consumes complex power 620∠29° VA: find apparent, real and reactive power and pf, say whether pf is leading or lagging, and draw the power phasor diagram
- An RL load on 60 Hz reads 120 V on the voltmeter, 6.3 A on the ammeter and 560 W on the wattmeter: find pf, leading or lagging, P, |S| and Q, draw the phasor diagram, and add the component (with value) that corrects pf to 1 without changing real power
- A 1.2 A, 400 Hz current source drives 100 Ω in parallel with 2 µF: find complex, real, reactive and apparent power and draw the power phasor diagram
- vs = 155.6 V cos(377t) drives a load of 4.6 Ω in series with 800 µF: find the load impedance and the average power
- A load draws 12 kVA at 0.8 pf lagging from 480 V; a parallel capacitor corrects pf to 0.9 lagging: find the capacitor's reactive power (with phasor diagram) and its capacitance at 60 Hz
- A 110 V rms source with 4 Ω internal resistance drives a load of 24 Ω in parallel with 100 µF at ω = 377 rad/s: find the average load power and the power lost in the source resistance
PA2: Transformers
- Read text sections 2.28 and 3.8 (the text draws secondary windings and currents backwards)
- An ideal transformer with 330 primary and 36 secondary turns is driven by 110 V rms: find the secondary voltage
- N1 = 320, N2 = 1000 and v(t) = 255 V cos(ωt) on the primary: find the rms secondary voltage
- A step-up transformer gives 2200 V rms from 240 V rms with 150 primary turns: find the secondary turns, and the primary current when the load draws 1.2 A
- An ideal transformer has 8.5 A and 80 V on the primary and delivers 1.0 A to a load resistor: find the secondary voltage
- Turns ratio N1/N2 = 1.5 with a 200 Ω load run at 150 V rms: find secondary and primary currents, source voltage, load and source power, and the input impedance two ways (N²ZL and V1/I1)
- vs(t) = 320 V cos(377t) feeds a 2.5:1 ideal transformer through a 100 Ω series resistor, with 25 Ω on the secondary: find vo(t)
- An ideal 120/30 V, 80 VA transformer is driven by 120 V through a 60 Ω primary resistor and loaded with 15 Ω: find I1 and V2
- A 13,800/480 V, 60 kVA transformer is supplied at 12,000 V: find the allowable primary and secondary currents at pf 1 and at pf 0.5
- An ideal 500/125 V, 10 kVA transformer with 440 V rms on the primary feeds a 5 Ω load at pf 0.80: find load voltage, load current, kVA and power to the load, primary current, primary pf, and the impedance seen at the primary
- A transformer rated 400 kVA at 460 V: find the maximum current, the maximum power at pf 1, 0.8 lagging and 0.7 lagging, and the minimum pf for a 300 kW customer
- An ideal 240/80 V, 100 VA transformer is driven by 120 V through a 40 Ω primary resistor and loaded with ZL = 12 + j20 Ω: find |I1|, |V1|, |V2|, source power, source pf (leading or lagging), and whether the transformer is within its ratings